S-Line Fire Pillows are an ideal product to create a temporary or permanent fire barrier around many types of services to prevent the passage of fire through a compartment wall or floor, especially suitable where services are continuously being changed or replaced. S-Line Fire Pillows are filled with organic fillers and reactive intumescent additives in a PU glass cloth case.
Packaging: Sizes as above table in boxes of 25 or 50
Colour: Silver, white, black or red by request
Fire Resistance: EI 120, 240mins
Insulation: 120mins
Classification: EN 13501-2
Acoustic Isolation: 46dB
Air Permeability: 420Pa, 100Pa 22.8/31.1 m3/h/m2
Expected Shelf Life: N/A
Measurement: 330 x 200 x 25mm
Key Product Points:
Can be used in rigid walls and floors
Can be used with Metallic Pipes, Cables, Cable Bunches, Cable Trays and Cable Ladders
Reaction Temperature 180°
High expansion ratio
Remains flexible between -20° to +130°C
Water resistant lining
Suitable for locations up to 1m²
Non-combustible and non-toxic
Ease of installation and long life
Key Installation Points:
For good adhesion the surfaces of the building elements shall be free of any dust or grease and may need to be primed. On good, clean virgin concrete and masonry, no priming required
Ensure that the aperture and services in question are tested with S-Line Pillows and the site conditions are within the application specification
Upon installation make sure that you install the S-Line Fire Pillow length ways to the recommended installation method for the service you are installing around
Install the S-Line Fire Pillows in such a way that all joints are staggered in each layer until you have filled all gaps within the wall. Pack pillows tightly into the opening around the services to a minimum depth of 150mm. Always ensure that large voids are completely filled and S-Line pillows are installed in a manner that ensures a tight compression fit
For floor:
Install a 5mm mild steel mesh securely fastened to rigid floor
Arrange S-Line Pillows in such a manner that they fully fill the penetration voids to a minimum depth of 150mm on the mesh
When cable trunking passes through the seal ensure that the inside is filled with S-Line Sausage Pillows