PS Coating is an ablative coating applied to stone wool board to be used to reinstate the fire resistance performance of wall constructions where apertures exist with penetration of single or multiple services.
Spray Pressure: Machine 90psi / Tip 6000psi / Tip Size 0.85mm
Installation on Specification: 50mm Stone Wool - EI 60, 100mm Stone Wool - EI 120
VOC % Nonaqueous volatiles (105°C): 4.9
Expected Shelf Life: 12 months
Key product points:
PS Coating is an easy to apply highly viscous, or thick coating suitable to be applied by brush
Key Product Points
Can be brush or trowel applied
Suitable for indoor use without additional environmental protection
Remains flexible between -5°c to +70°c
Easy to use fibre free coating
Suitable for large openings in wall systems such as in combination with Stopseal Batt
Key Installation Points:
For good adhesion the surfaces of the building elements shall be free of any dust or grease and may need to be primed. On good, clean virgin concrete and masonry, no priming required, though refer to substrate compatibility requirements
Ensure that the aperture and services in question are tested with PS Coating and the site conditions are within the application specification
Upon installation make sure that you install the minimum 140kg/m³ Stone Wool
Fit around all services effectively, brush or trowel over the stone wool ensuring all joints and junctions are fully covered to the minimum required PS Coating thickness
Ensure PS Coating Sealant is applied to a minimum
Stone Wool minimum 140kg/m³ maybe pre coated off site, applying some PS Coating to aid during installation. Ensure the correct thickness of PS Coating is applied after site installation